Package Chilled Water  Horizontal Exposed Fan Coil Unit Ceiling installation

 

Specifications

 

 

Model
Performance
EKCW200EC EKCW300EC EKCW400EC EKCW500EC EKCW600EC EKCW800EC EKCW1000EC EKCW1200EC EKCW1400EC
Rated air flow (m3/h) H 340 510 680 850 1020 1360 1700 2040 2380
M 279 418 558 697 836 1115 1394 1673 1952
L 170 255 340 425 510 680 850 1020 1190
Rated cooling capacity (W) Total heating/
cooling capacity
H 2260 3480 4490 5140 6450 8490 10030 11540 13600
Sensible heating/
cooling capacity
H 1490 2170 2870 3600 4370 6080 7110 8500 9920
Rated heating capacity (W) H 3610 5480 7050 7900 9770 13210 16230 18160 21810
Rated input power (W) H 39 53 72 83 107 142 183 217 239
Working current (A) H 0.18 0.24 0.33 0.38 0.48 0.65 0.83 0.99 1.09
Sound dB(A) H 37.0 39.0 42.0 43.0 46.0 45.5 50.0 50.0 52.0
Water flow (m3/h) 0.44 0.61 0.74 Package Chilled Water Horizontal Exposed Fan Coil Unit Ceiling installation
Tips:This page [Package Chilled Water Horizontal Exposed Fan Coil Unit Ceiling installation] infomation provided by [EuroKlimat Air Conditioning Refrigeration Company] ,the enterprise is responsible for the authenticity, accuracy and validity of the information content. Worldinout.COM do not assume any guarantee of joint and several liability. A safe way to suggest that the two sides trade, to ensure the interests of both sides.